noscript
PVC Coated TB Form Conduit Bodies

Features

  • Exterior PVC coating thickness is a minimum 0.040″
  • Interior urethane coating thickness is a minimum 0.002″
  • Specialized corrosion resistant coating provided on threads
  • Sizes available are 1/2″ to 2″
  • Fittings are supplied with plastic encapsulated stainless steel screws

Applications

Calbond offers the full line of TB Form 7 PVC Coated Conduit Bodies. Conduit Bodies are installed in conduit systems to; act as pull outlets for conductors being installed, provide openings for making splices in conductors, and to provide access to conductors for maintenance and future system changes. All fittings are supplied with PVC coated cast iron covers. The sleeved threaded ends offer complete protection against corrosion while maintaining full ground continuity throughout the installed system.

Standards

  • UL Standard 514B
  • CSA Standard: C22.2 No. 18

PVC Coated TB Form 7 Fittings

Item NumberTrade Size (in)Metric Size (mm)ABCDEWeight Per 100 (lbs)
Steel
PV0500TB171/2166.632.671.640.943.19160
PV0700TB273/4217.752.921.831.133.81210
PV1000TB371279.253.292.081.384.5270
PV1200TB471-1/4359.943.352.271.755370
PV1500TB571-1/24111.195.042.521.945.44470
PV2000TB6725313.196.173.082.446.38700
Aluminum
PA0500TB17SA1/2166.632.671.640.943.19Contact Factory
PA0700TB27SA3/4217.752.921.831.133.81Contact Factory
PA1000TB37SA1279.253.292.081.384.5Contact Factory
PA1200TB47SA1-1/4359.943.352.271.755Contact Factory
PA1500TB57SA1-1/24111.195.042.521.945.44Contact Factory
PA2000TB67SA25313.196.173.082.446.38Contact Factory