noscript
PVC Coated T Form Conduit Bodies

Features

  • Exterior PVC coating thickness is a minimum 0.040″
  • Interior urethane coating thickness is a minimum 0.002″
  • Specialized corrosion resistant coating provided on threads
  • Fittings are supplied with plastic encapsulated stainless steel screws
  • Sizes available are 1/2″ to 4″
  • 3-1/2″ and 4″ in PVC Coated Aluminum Mark 9 only

Applications

Calbond offers the full line of T Form 8 PVC Coated Conduit Bodies. Conduit Bodies are installed in conduit systems to; act as pull outlets for conductors being installed, provide openings for making splices in conductors, and to provide access to conductors for maintenance and future system changes. All fittings are supplied with PVC coated cast iron covers. The sleeved threaded ends offer complete protection against corrosion while maintaining full ground continuity throughout the installed system.

Standards

  • UL Listed Standard 514B File# 307133
  • CSA Standard: C22.2 No. 18
  • Verified NEMA 4X Rated

PVC Coated T Form 8 Fittings

Item NumberTrade Size (in)Metric Size (mm)ABCDEWeight Per 100 (lbs)
PV4000T10894103245.988.175.4413.442400
PV3500T9893-1/291215.738.175.4413.442350
PV3000T8837823.14.856.734.2510.882100
PV2500T782-1/26319.84.486.734.2510.881980
PV2000T6825311.73.65.0438.561170
PV1500T581-1/2417.52.824.042.136.5750
PV1200T4481-1/4351.92.673.21.755.31490
PV1000T381273.32.292.671.384.56330
PV0700T283/4212.52.042.351.193.94250
PV0500T181/2166.691.792.213.31180